In data centers the entire electrical-kilowatt-power input to computer equipment is converted to heat and discharged into a conditioned space. Most small and medium-size data-processing centers utilize direct-expansion computer-room air conditioners - typically, split-air, water, or glycol-cooled. Large data centers predominantly utilize chilled-water-room units for several reasons, including:
|
| Per American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) standards, typical data-center HVAC design conditions (68 to 77°F, 40- to 45-percent relative humidity) are required day and night, 365 days a year. Chilled-water temperature usually is required to be 45 to 50°F, depending on the computer-room-air-conditioning (CRAC) unit coil design for cooling and dehumidification. This continuous temperature- and humidity-control requirement also allows the possibility of substantial energy savings.
Two significant energy-saving possibilities for chilled-water systems are the use of free-cooling chillers and simultaneous heat-recovery chillers for dehumidification.
|
Free Cooling:
 |
Supercooler as freecooling module placed on a roof |
|
The continuous cooling demand of data centers is largely unchanged during winter because winter building losses do not have a significant effect on total heat load. With the application of a free-cooling circuit to a central chiller, refrigeration compressors can be switched off for long periods of time during winter, spring, and fall. A water-cooled central chiller can be designed to switch automatically to free cooling as soon as a cooling tower's cooling water or glycol is at or below the return chilled-water temperature, while an air-cooled chiller with an integrated or separate free-cooling coil can switch to free cooling when the outside ambient temperature is lower than the return chilled-water temperature. Both of these energy-efficient designs for large data center HVAC systems have similar advantages, including a direct reduction in energy costs and fewer compressor running hours. Further, the refrigeration compressors in an air-cooled chiller are never required to operate in very cold ambient temperatures, which eliminates any special low-temperature refrigeration controls and extends the equipment's life expectancy by eliminating the most difficult operating conditions for an air-cooled system.
Example:
Consider the savings possible in a New York City data center with 20 25-ton chilled-water CRAC units. This represents an installed cooling capacity of 500 tons. ASHRAE's historical weather data in New York City suggests a 99-percent winter design dry-bulb temperature of 11°F and an average of 3,750 hr of dry-bulb temperatures below 40°F per year. The chilled-water CRAC units typically require approximately 50°F chilled-water-supply and 60°F chilled-water-return temperatures. This means an ideal situation exists for winter free-cooling chiller savings. |
System I : direct expansion closed control units with aircooled condensers
 |
For small / medium thermal loads (max. 30 kW IT - load ) |
 |
Redudancy only with complete doubled systems |
 |
Strong dehumidification cause of low evaporations temperature |
 |
Humidification and heating neccessary with high operation costs |
 |
Low invest, but high operating costs cause of energy and maintenance |
 |
No emergancy-cooling-operation possible in case of blackout. |
| |
|
|

|
|
System II : DX – closed control units with free cooling exchanger and glycol cooler
 |
For medium IT-load & single rooms up to ca. 80 kW |
 |
Bad for placing in the serverroom because of high effort in |
 |
Maintenance and service |
 |
Later extension (for increasing loads) not possible |
 |
Same else system |
 |
Relativ low invest, but also high operating costs because of stronger fans, |
| |
circulatingpumps + high effort in maintenance |
|
System III : central water chiller system with free cooling and watercooled closed control units
 |
Very flexible system for IT-loads from up 50 kW until 2.000 kW |
| |
(and bigger) with using of free cooling |
 |
Very good controling of the performance with (n+1) water chiller |
| |
and closed control units |
 |
Emergancy running with buffertank and ups-buffered closed control |
| |
units and circulation pumps |
 |
Sensible operation with chilled water 12/18 °C & high coefficent by |
| |
using screw- or scroll compressor |
 |
Relativ high first-invest cost but minimum service- and maintenance cost |
|
 |
|
System IV : central water chiller system with free cooling
 |
Flexible cooling systems for IT loads from up 80 kW until 2.000 kW with |
| |
energyefficience free cooling |
 |
Similar system configuration and operating costs like central water |
| |
chiller system |
 |
Less space for installation inside of the builing necessary |
 |
High quality cooling technology, Placed weatherproofed outside |
|
|
|