Aspirating Smoke Detection
Offering earliest fire detection, very high sensitivity, counter measuring of time, letest detection technology, false alarm free detection technology, false alarm free detection, innovative air flow sensor, easy commisoning and maintenance and modular system setup. The systems are available for room observation aswell as for in-rack detection.
Early Fire Detection by WAGNER Smoke Detection Systems:
Fire detection is the core of fire prevention measures. WAGNER has been the innovative leader for many years and possesses some of the most powerful systems in the international market. |
|
TITANUSŪ Concept:
Each Moment Counts..
Early detection is necessary for possible fire suppression - this decides the amount of damage. To support this, WAGNER has placed its confidence in early smoke detection systems.
|
|
Being Quick Means Minimising Damage
Early fire detection minimises damage since measures can be taken much earlier. The protection of people, irreplaceable assets and operational continuity is guaranteed. A fire must be reliably detected in its initial phase so that immediate and efficient measures can be taken. |
|
Smoke - always first when a fire occurs
A fire is always accompanied by smoke, heat, and light (the fire characteristics).
Smoke already appears in relatively large quantities at an early stage of a fire and can
reliably be detected by optical detectors. That is why smoke is the perfect fire
characteristic for early fire detection. |
|
Fire Detection - Operation
Quicker and more efficient than point-type detectors:
WAGNER relies on air sampling systems for smoke detection. Via a pipe system the air sampling smoke
detection system actively takes air samples from the risk and passes them to an optical
chamber.
Detection without false alarms:
In contrast to point-type detectors which can be limited in their environmental applications air sampling smoke detection systems can possess a higher sensitivity - leading to quick and reliable fire detection!
Particularly suitable for difficult environments:
In difficult environments such as high ceilings, extreme temperatures, dirt and humidity or high aesthetic requirements an air sampling smoke detection system can produce reliable fire detection.
|
Environmental influences eliminated:
Environmental conditions that can produce unwanted alarms can be eliminated (using technology, professional engineering, sophisticated pipe accessories). Optimal results can be reached by using a sensitivity and system suitable for the specific application.
|
Clean Rooms:
 |
Safe smoke detection despite forced air flow and high air speed |
 |
No air contamination within the production area due to active air sampling of the room's outgoing air |
 |
Maintenance and service personnel do not need to enter the clean room |
|
|
Products:
Titanus- Family -The New generation:
With the newly developed High-Power-Light-Source, the sensitive smoke sampling systems of the TITANUSŪ family ensure early detection for the whole spectrum of possible fires.
|
Advantages:
 |
Innovative detection technology using a newly developed High-Power-Light-Source |
 |
A detector module specially developed for use with air sampling smoke detection systems |
 |
Ordinary commissioning and maintenance |
 |
VDS approved |
 |
Provided with LOGIC·SENS intelligent signal processing |
 |
Innovative air flow sensor and closed circuit air path |
 |
User operated diagnostic tool provides fast and simple servicing |
|
|
Titanus Pro-Sens:
Universal air sampling smoke detection. Provided with LOGIC·SENS intelligent signal processing.
Performance Characterstics:
 |
Potential free relay outputs for alarm- and fault signalling to house fire alarm system |
 |
One or two detection zones |
 |
Up to 64 air sampling points per system possible, maximum pipe length 560 metres |
 |
Monitored area air sampling point is the same as a point-type detector(depending on operating mode) |
 |
Detector sensitivity:0.05 %LO/m, display sensitivity: 0.05%LO/m, max. area: 4800 m2 per ASD |
 |
Optional networking ability |
|
Titanus Top-Sens:
Sensitive smoke sampling system with graded alarm and bar graph display. Provided with LOGIC·SENS intelligent signal processing.
Performance Characterstics:
 |
Potential free relay outputs for alarm and fault signalling to house fire alarm system |
 |
10-level alarm display with activating thresholds for alert, action and fire-alarm |
 |
Detector sensitivity : 0.05 %LO/m, display sensitivity: 0.005%LO/m, max. area: 4800 mē per ASD |
 |
Optional netwotking ability |
 |
True coincidence detection possible |
 |
One or two detection zones |
|
 |
 |
Up to 64 air sampling points per system possible, maximum pipe length 560 metres |
 |
Monitored area air sampling point is the same as a point-type detector (depending on operating mode) |
 |
Single hole fault monitoring equivalent to point type detection |
 |
Detector sensitivity : 0.5 %LO/m, display sensitivity: 0.05%LO/m, max. area: 400 mē per ASD |
 |
Individual adjustment of response |
 |
Maintenance with interactive diagnosis means no interruption of operations |
 |
Central monitoring, remote diagnosis and remote maintenance by networking |
 |
Optional use of second detector module for dual detector voting |
 |
Fire detection and extinguishing in a single device (88,9 mm construction height (2U) |
 |
Choice of extinguishing gases: 44,45 mm construction height (1U) device with external extinguishing: Novec 1230, FM-200, Nitrogen, Argon or Carbon Dioxide. 88,9 mm construction height (2U) device with built-in extinguishing: Novec 1230, FM-200 |
 |
Detector sensitivity : 0.1 %LO/m, display sensitivity: 0.01%LO/m, max. area: up to 5 connected racks |
|
|
|